Material
FR4 fiberglass panels, aluminum plate, copper substrate, iron substrate, PTFE, F4B, F4BM, Kangtai Li, CER-10, Rogers, FPC soft board and some other high-precision plate.
Crafts
Light copper, nickel, gold, tin spray; Immersion Gold, antioxidant, HASL, immersion tin, etc.
Double Layer PCB Leadfree HASL with blue solder mask
- Leadfree HASL Surface finish required to meet ROHS compliant
-FR-4 material with 0.25mm-6mm boards thickness
-Copper weight:1/3OZ,0.5OZ,1OZ,2OZ,3OZ,4OZ,5OZ,6OZ
-3-3mils min track width & spacing -0.2mm min finished hole size
-Certificate: UL,ISO14001,TS16949 and ROHS
-Company management: ISO9001
-Markets: Europe, America, Asia,etc.
Application
electronic products, like
computer peripherals,aerospace,telecommunication,automotives,medicaldevices,camermas,optoelectronic devices,VCD,LCD and verious other comsumer electronic products.
Product Details:
Payment & Shipping Terms:
|
| Type: | High Frequency Online UPS | Phase: | Three Phase |
|---|---|---|---|
| Wave Form: | Pure Sine Wave | Cabinet: | Metal |
| Highlight: | industrial ups systems,online ups power supply |
||
High Frequency Online UPS Queen Star Plus Strar Series 33Q10K-80K(3Ph in/3Ph out)
Key Features
1: Generator compatible
2: Accepts dual power inputs
3: Perfect battery charge management.
4: Adopt 4 layers PCB, and SMD technology
5:Active input power factor correction(PFC)
6: SNMP+USB+RS-232 multiple communications
7: Alarm High-low Battery Input Voltage Protection Function
8: Environment Friendly and Energy Saving Technology Know-How
9: 3-stage extendable charging design for optimized battery performance
10:Advanced automatic constant charging circuit, prolongs battery life
11:Perfect protection against battery under voltage, overload and short circuit.
12:Auto restart after utility power restore when UPS shutdown due to battery low
Applications;
Alarm System, Building Automation System BAS, weak electricity system integration, CTP, PLC (Programmable Logic Controller), DDC (Direct Digital Control System), Data Center, manufacture industry, petrochemical system, metallurgical industry etc.
| Technical Specification: | |||||||
| Index | 33Q 10KL | 33Q 20KL | 33Q 30KL | 33Q 40KL | 33Q 60KL | 33Q 80KL | Comments |
| Input | |||||||
| Input voltage | |||||||
| Rated voltage | 380VAC/220VAC | 380VAC | |||||
| Phase | three phase with ground | ||||||
| Turn on voltage range |
(120±5~274±5)VAC | (207±9~475±9) VAC |
|||||
| Bypass voltage range |
(60±5~300±5)VAC | (105±9~518±9) VAC |
Could be adjusted by software. |
||||
| Bypass low loss |
60VAC~220VAC(default 60VAC) | 105VAC~380VAC (default 105VAC) |
|||||
| Bypass low comeback |
Low loss +5VAC | Low loss +17VAC |
|||||
| Bypass high loss |
220VAC~300VAC(default 300VAC) | 380VAC~475VAC (default 475VAC) |
|||||
| Bypass high comeback |
High loss -5VAC | High loss -17VAC | |||||
| Line low loss comeback |
(120±5) VAC /(140±5) VAC | (207±9) VAC (242±9) VAC |
load≤50% | ||||
| (140±5) VAC /(160±5) VAC | (242±9) VAC (276±9) VAC |
50%≤90% | |||||
| (160±5) VAC /(175±5) VAC | (276±9) VAC (302±9) VAC |
load>90% | |||||
| Line high loss comeback |
(275±5)VAC/(260±5)VAC | (475±9)VAC (449±9)VAC |
|||||
| Input frequency | |||||||
| Rated frequency |
50Hz | ||||||
| Frequency low loss |
(40~49) ±0.2Hz(default:46Hz) | Could be adjusted by software. |
|||||
| Frequency low comeback |
Frequency low loss +0.5Hz | ||||||
| Frequency high loss |
(51~60)±0.2Hz(default:54Hz) | ||||||
| Frequency high comeback |
Frequency high loss -0.5Hz | ||||||
| Input power factor | |||||||
| Could be adjusted by software. |
> 0.99 | 33Q 10-40KL: 220VAC,full R load 33Q 60-80KL: 380VAC,full R load |
|||||
| Generator | Support generator input | Generator rating ≥2*UPS rating |
|||||
| Input current | |||||||
| Rated current | 14A | 28A | 42A | 67A | 80A | 105A | |
| Input THDI | <= 10% | ||||||
| Output protection | |||||||
| Rating protection |
32A Breaker |
50A Breaker |
60A Breaker |
80A Breaker |
100A Breaker |
125A Breaker |
|
| Output power | |||||||
| VA/watt | 10KVA/8KW | 20KVA/16KW | 30KVA/24KW | 40KVA/32KW | 60KVA/ 48KW |
80KVA/ 64KW |
|
| Rated voltage | 220VAC | 380VAC | Sine wave | ||||
| Voltage range | 200/208/220 /230/240VAC |
345/359/380 /397/415 VAC |
33Q 10-40KL: Could be adjusted by software. 10% derating for 208VAC /200VAC. 33Q 60-80KL: Could be adjusted by software. 10% derating for 345VAC /359VAC. |
||||
| Voltage regulation | ±1% | ||||||
| Voltage distortion | ≤5% | ≤10% | Full RCD load | ||||
| ≤3% | Full R load | ||||||
| DC offset | ≤200mV | ||||||
| Transient response | ≤9% | R load 0%~100%~0% |
|||||
| ≤6% | R load 20% ~100%~20% |
||||||
| Transient recovery | ≤60ms voltage recovery to 90% | Full RCD load | |||||
| Bypass output before turn-on |
YES | ||||||
| Crest ration | 3:1 | ||||||
| Output frequency range | |||||||
| Normal mode | 1,Same as input frequency(46Hz~54Hz) 2,50Hz(Input frequency>54Hz or Input frequency<46Hz) |
||||||
| Battery mode | (50±0.1) Hz | ||||||
| Slew rate | 1 Hz/Sec | ||||||
| Efficiency | |||||||
| Normal mode | > 93% | > 90% | |||||
| Battery mode | > 90% | > 90% | |||||
| Overload | |||||||
| Normal mode battery mode |
Overload warning only | 105%±5%≤load | |||||
| 1min,then transfer to bypass and alarm. | 105%±5%< load≤125%±5% |
||||||
| 30S,then transfer to bypass and alarm. | 125%±5%< load≤150%±5% |
||||||
| 300mS, then transfer to bypass and alarm. | load>150%±5% | ||||||
| Automatically retransfer |
YES | ||||||
| Short protection | |||||||
| Normal battery mode |
YES | ||||||
| Transfer time | |||||||
| Normal to battery mode |
0mS | ||||||
| Battery to normal mode |
0mS | ||||||
| Normal to bypass mode |
<4mS | 0mS | |||||
| Bypass to normal mode |
<4mS | 0mS | |||||
| Battery and charger | |||||||
| Battery | |||||||
| Rated voltage | 192VDC | 240VDC | 192VDC*2 | 192VDC*2 | 480VDC | ||
| Type/Rating | |||||||
| Battery quantity |
16 | 20 | 16*2 | 16*2 | 40 | ||
| Backup time | |||||||
| Protection | |||||||
| Low alarm voltage comeback voltage |
(180.8V±4V)/ (188.8V±4V) | (226V±4V)/ (236V±4V) | (180.8V±4V) (188.8V±4V) |
(226V±4V)/ (236V±4V) | (452V±4V) (472V±4V) |
33Q 30KL use two |
|
| Shutdown voltage comeback voltage |
160V±4V/ 168V±4V |
(200V±4V)/ (210V±4V) | 160V±4V/ 168V±4V |
(200V±4V)/ (210V±4V) | (400V±4V) (420V±4V) |
||
| DC protection | |||||||
| Overcharge protection comeback voltage |
(249.6V±4V) (216V±4V) |
(312V±4V) (270V±4V) | (249.6V±4V) (216V±4V) |
(312V±4V) (270V±4V) | (624V±4V) (540V±4V) |
||
| Leakage current | < 500uA | ||||||
| Over discharge protection |
14.5h | Could be set by software |
|||||
| Battery test | |||||||
| Battery weak | YES | ||||||
| Battery fault | YES | ||||||
| Charger | |||||||
| Output voltage | (219.2±3)VDC | (277±3)VDC | (219.2±3)VDC | (277±3)VDC | (554±3)VDC | ||
| Charge time | Depends on the external battery capacity | ||||||
| Charge current | 7.5A | 6A | 5A | 4A | 10A | ||
| Interface | |||||||
| Alarm silence | YES | ||||||
| DC power turn-on |
YES | ||||||
| Automatically retransfer |
YES | ||||||
| Audio alarm | |||||||
| Battery mode | Beep/4s | ||||||
| Battery low charger fault |
Beep/1s | ||||||
| UPS fault | Continue beep | ||||||
| Overload | Beep/1s | ||||||
| Bypass mode | Beep/2Min | ||||||
| L/N inverse | Beep/2Min | ||||||
| Communication | |||||||
| RS232 interface | YES | ||||||
| Intelligent slot | YES | ||||||
| Monitor software | Appending with UPS | ||||||
| Cooling | |||||||
| Force air cooling | |||||||
| Display | |||||||
| LCD/LED displays UPS status | |||||||
| Environment | |||||||
| Work temperature |
0ºC~40ºC | ||||||
| Altitude | <1000m | ||||||
| Audible noise |
≤60dB | ||||||
| Storage temperature |
-15ºC~45ºC | ||||||
| Work humidity | 20%~95% | ||||||
| Standard | |||||||
| EMS | |||||||
| ESD | IEC61000-4-2 | Level4 | |||||
| RS | IEC61000-4-3 | Level3 | |||||
| EFT | IEC61000-4-4 | Level4 | |||||
| Surge | IEC61000-4-5 | Level4 | |||||
| EMI | |||||||
| Conducted | EN55022 | Class A | |||||
| Radiated | EN55022 | Class A | |||||
| Safety | |||||||
| Safety | GB4943-2001/IEC62040-1 | ||||||
| Machinery features | |||||||
| Size | |||||||
| Outline dimension and net weight | |||||||
| L*W*H (mm) | 710*260*717 | 840*515*1135 | |||||
| Net weight(Kg) | 45/93 | 50/98 | 195 | 208 | |||
| Optional functions | |||||||
| 60Hz | Optional | Set by software | |||||
| Converter mode | Optional | Set by software | |||||
| ECO | Optional | Optional | Available and set by software |
||||
| EPO | Optional | Optional | |||||
| LCD display | Optional | ||||||
Contact Person: Miss. aaa
Tel: 86 755 8546321
Fax: 86-10-66557788-2345